HRL 12390W is specially designed for high efficient discharge and long life.application. It\'s characteristics are small volume, light weight and high discharge efficiency. It can be used for more than 260 cycles at 100% discharge in cycle service, up to 10 years in standby service.
CSB Batteries can be stored for more than 6 months at 25℃(77°F). Please charge batteries before using. For higher temperatures the time interval will be shorter.
Terminal
I2-Thread lead alloy recessed terminal to accept M6/M8 bolt
Container Material
Polypropylene(UL 94-V0/File E50955)*Flammability resistance of (UL 94-HB/File E216959) can be available upon request.
Dimensions
Constant
Current Discharge Characteristics Unit:Amperes (25°C,77°F)
F.V/Time
5MIN
10MIN
15MIN
20MIN
30MIN
40MIN
45MIN
50MIN
60MIN
90MIN
1.60V
443.00
308.00
236.00
191.00
142.00
112.00
102.00
93.50
78.80
58.00
1.67V
398.30
285.40
222.60
182.00
134.30
108.00
97.10
88.80
75.10
54.10
1.70V
376.00
273.80
214.60
177.00
130.00
105.00
94.60
86.40
72.20
51.40
1.75V
336.20
253.70
203.00
166.76
122.20
99.30
90.76
82.20
69.18
49.10
1.80V
294.50
232.30
187.49
154.00
113.50
92.20
83.75
76.40
64.71
45.60
1.85V
254.00
209.89
171.39
141.00
104.71
85.80
78.16
71.61
60.67
43.40
Constant
Power Discharge Characteristics Unit:Watts (25°C,77°F)